| Class CPR acc. to UE 305/2011 (DoP) | Eca | |
| Availability | in stock | |
| Application | Primary (Campus), Secondary (Riser), Tertiary (Horizontal) | |
| IPTV; HbbTV 2.0.n | ||
| IEEE 802.3: 10Base-T; 100Base-T; 1000Base-T | ||
| IEEE 802.5 16 MB: ISDN; TPDDI; ATM; PoE | ||
| Indoor + Outdoor Installation | ||
| acc. to Standard | ISO/IEC 11801 Class D | |
| EN 50288-2-1 | ||
| EN 50173 | ||
| EIA-TIA 568 | ||
| CEI-UNEL 36762 | ||
| Reaction to Fire | EN50575 | |
| CONSTRUCTION DATA | ||
| Inner Conductor | Ø mm | 0,51 |
| material | Cu | |
| Insulation | Ø mm | 1,00 |
| material | PE | |
| Film Foil Laminate | material | Pet |
| Film Foil | material | AP |
| Outer Sheath | Ø mm | 6,2 |
| material | LSZH | |
| PHYSICAL DATA | ||
| Copper Content | kg/km | 15,6 |
| Cable Weight | kg/km | 40,2 |
| Min bending radius x 1/n | mm | 25/50 |
| Max.Tensile Strength | N | 100 |
| ELECTRICAL DATA | ||
| Impedance | Ohm | 100±5@100 MHz |
| Capacitance of Twisted Pair (@800Hz) | pF/m | 48 |
| Velocity Ratio | % | 67 |
| Attenuation (at 20°C ) | ||
| at 1 MHz | dB/100m | 1,9 |
| at 10 MHz | dB/100m | 6,0 |
| at 20 MHz | dB/100m | 8,5 |
| at 31,2 MHz | dB/100m | 10,7 |
| at 62,5 MHz | dB/100m | 15,7 |
| at 100 MHz | dB/100m | 19,8 |
| NEXT | ||
| at 1 MHz | dB | 71,0 |
| at 10 MHz | dB | 56,0 |
| at 20 MHz | dB | 51,0 |
| at 31,2 MHz | dB | 49,0 |
| at 62,5 MHz | dB | 44,0 |
| at 100 MHz | dB | 41,0 |
| Coupling Attenuation | dB | > 45 |
| Transfer Impedance (Zt) | ||
| 1 MHz | mOhm/m | < 22 |
| 10 MHz | mOhm/m | < 10 |
| 30 MHz | mOhm/m | < 26 |
| Screening Attenuation (SA) | ||
| at 30 - 100 MHz | dB | > 50 |
| DC Conductor Resistance | Ohm/km | 95,0 |
| Loop resistance | Ohm/km | 190,0 |
| Sheath Insulation Voltage (DC, 1 min) | kV | 1,0 |
Cat. 5e F/UTP 4x2xAWG24/1