Availability | on demand | |
Application | Work area, patch cord cable | |
IEEE 802.3: 10Base-T; 100Base-T; 1000Base-T | ||
IEEE 802.5 16 MB: ISDN; TPDDI; ATM; PoE | ||
Indoor + Outdoor Installation | ||
acc. to Standard | EN 50288-6-2 | |
EN50173 | ||
CEI-UNEL 36762 | ||
EN50575 | ||
CONSTRUCTION DATA | ||
Inner Conductor | Ø mm | 0,60 7x0,20 |
material | Cu | |
Dielectric | Ø mm | 1,05 |
material | PE | |
Outer Sheath | Ø mm | 6,8 |
material | LSZH | |
PHYSICAL DATA | ||
Copper Content | kg/km | 17,3 |
Cable Weight | kg/km | 48,1 |
Min bending radius x 1/n | mm | 34/68 |
Max.Tensile Strength | N | 100 |
ELECTRICAL DATA | ||
Impedance | Ohm | 100±5@100 MHz |
Capacitance of Twisted Pair (@800Hz) | pF/m | 48 |
Velocity Ratio | % | 67 |
Attenuation (at 20°C ) | ||
at 10 MHz | dB/10m | 0,9 |
at 20 MHz | dB/10m | 1,28 |
at 31,2 MHz | dB/10m | 1,61 |
at 62,5 MHz | dB/10m | 2,32 |
at 100 MHz | dB/10m | 2,99 |
at 155,5 MHz | dB/10m | 3,79 |
at 250 MHz | dB/10m | 4,95 |
NEXT | ||
at 10 MHz | dB | 60,3 |
at 20 MHz | dB | 55,8 |
at 31,2 MHz | dB | 52,9 |
at 62,5 MHz | dB | 48,4 |
at 100 MHz | dB | 45,3 |
at 155,5 MHz | dB | 42,4 |
at 250 MHz | dB | 39,3 |
Coupling Attenuation | dB | > 45 |
DC Conductor Resistance | Ohm/km | 85,0 |
Loop resistance | Ohm/km | 170,0 |
Sheath Insulation Voltage (DC, 1 min) | kV | 1,0 |
Cat. 6 Flexible U/UTP 4x2xAWG26/7